Temperature Adjustment Range: 35° to 45°Celsius
Inlet Temperatures Cold Supply: 5°C - 25°C Hot Supply: 60°C - 90°C
Hot to Mix Temperature Differential for Stable operation: Minimum 10°C
Cold to Mix Temperature Differential for stable operation: Minimum 5°C
Flow Rates To ensure stable outlet conditions: Minimum 4 /minute
Dynamic Inlet Pressures Hot and Cold Inlet Pressures: Minimum 20 kPa Maximum 500 kPa
Static Inlet Pressure Hot and Cold Inlet Pressures: Maximum 1000 kPa
Inlet Pressure Ratio Maximum inlet pressure ratio for stable operation (Hot: Cold or Cold: Hot) 0:1 (either supply)
For optimum operation it is recommended that the hot and cold water supply pressures be balanced to within +/- 10%.
Notwithstanding the above, compliance with AS3500 must be maintained.
Inlet & Outlet 15mm 1/2" Copper Tails
Lockable and easily removable stainless steel access door fitted.
Refer below for technical information & download
AVG TMV15BP-PIB Bypass Thermostatic Mixing Valve in Stainless Box 15mm 1/2" plumbed into a standard 350mm square x 75 deep stainless steel box. The same directional hot, cold and mixed connections as the standard PIB arrangements can be achieved and a bypass line with appropriate copper fittings fitted. Provides high stability of mixed water temperature even under changing inlet conditions. Ensures rapid shut down of mixed outlet flow in the event of hot, or cold water supply isolation. Easily serviced on site. Suitable for installation into AS3500 compliant systems with hot water temperature as low as 60°C• The adjustment mechanism can be locked to prevent tampering.
Plumbingsales will be closed from Friday 20th December and Re Open Monday 6th January. Orders can still be placed online during closure period and order processing will resume Monday 6th January.
Last stock orders will be dispatched Thursday 19th December before 3.00pm