Temperature Adjustment Range: 35° to 45°Celsius
Inlet Temperatures Cold Supply: 5°C - 25°C Hot Supply: 60°C - 90°C
Hot to Mix Temperature Differential for Stable operation: Minimum 10°C
Cold to Mix Temperature Differential for stable operation: Minimum 5°C
Flow Rates To ensure stable outlet conditions: Minimum 4L /minute
Dynamic Inlet Pressures Hot and Cold Inlet Pressures: Minimum 20 kPa Maximum 500 kPa
Static Inlet Pressure Hot and Cold Inlet Pressures: Maximum 1000 kPa
Inlet Pressure Ratio Maximum inlet pressure ratio for stable operation (Hot: Cold or Cold: Hot) 0:1 (either supply)
For optimum operation it is recommended that the hot and cold water supply pressures be balanced to within +/- 10%.
20mm 3/4" Inlet and Outlet
Refer download below for more information
AVG TMV20 Thermostatic Mixing Valve 20mm 3/4" Outlet is suitable for a wide range of applications. The valve is designed to comply with Australian Standard AS4032.1 and the NSW Health Department requirements. Provides high stability of mixed water temperature even under changing inlet conditions. Ensures rapid shut down of mixed outlet flow in the event of hot, or cold water supply isolation. Easily serviced on site. Suitable for installation into AS3500 compliant systems with hot water temperature as low as 60°C• The adjustment mechanism can be locked to prevent tampering.